Hiwin Renewable Power Inverter - 5kW
HIWIN Mikrosystem Renewable Energy Converter adopts RS485 human-manchine interface, LCD status display and transformerless design. Not only with PFC function and wide voltage range, it also reduces generator noise, matches well with generator, and is easy for installation since no need to install with wind energy transformer.
Renewable Power Inverter - 5kW
ดาวน์โหลดไฟล์ PDFFeatures | Renewable Power Inverter - 5kW
- Transformer-less design
- Wide input voltage range and better compatible with generators
- High speed MPPT control, rapidly capture renewable energy
- Woth PFC function, reduce noise from the generator
- Maximum conversion efficiency of 95%
- THD < 3%
- Automatically detects grid frequency 50/60 Hz
- LCD status display
- IP65 protection against dust and water
- HMI RS485 communication
Specifications | Renewable Power Inverter - 5kW
MODEL | HWI-500A-3 | |
---|---|---|
Input | Working voltage range | 90 - 345 Vac |
Maximum input voltage | 400 Vac | |
Nominal input current | 8.4 Aac | |
Maximum input current | 9.2 Aac | |
Number of MPPT | 1 | |
Standby power | < 10 W | |
Output | Nominal output power | 5000 W |
Maximum output power | 5500 W | |
Nominal output voltage | AC 230 / 400 V | |
Output voltage range | 186 - 264 Vac | |
Nominal output current | 7.2A | |
Maximum output current | 8A | |
Frequency | 50/60 Hz | |
Power factor | > 0.95 | |
Harmonic distortion | < 3 % (nominal power) | |
Output connector | 3-phase 4-wire (R, S, T, N, G) | |
Maximum Efficiency | 95% | |
Protection | Temperature | 40°C |
Grid system | Voltage abnormal, Frequency abnormal | |
Islanding | Passive detection Active detection |
|
Environment | Operating temperature range | -20 to 55 °C (-4 to 131 °F) (5kW rating apply at 40°C ambient temperature. At higher temperature (up to 55°C) the derating.) |
Altitude | 0 - 2000 m ; 0 - 6562 ft | |
Mechanical information | Dimension (H x W x D) | 640 x 480 x 240 mm |
Weight | 40 kg | |
Protection grade | IP65 | |
Cooling mode | Wind cooling | |
Other | Display | LCD, LED |
Communication | RS485 | |
Authenticate | Certificate | EN 61000-6-2 EN 61000-6-3 VDE AR-N-4105 IEC-62477-1 |